Installation, Maintenance, & Repair
Series 008QT and LF008QT
Spill-Resistant Pressure Vacuum Breaker
Sizes:
",
",
" and 1" (10, 15, 20, and 25mm)
3
1
3
8
2
4
Models: 008
!
WAR NI NG
You are required to thoroughly read all installation instructions
and product safety information before beginning the installa-
tion of this product. FAILURE TO COMPLY WITH PROPER
INSTALLATION AND MAINTENANCE INSTRUCTIONS
COULD RESULT IN PRODUCT FAILURE WHICH CAN
CAUSE PROPERTY DAMAGE, PERSONAL INJURY AND/
OR DEATH. Watts is not responsible for damages resulting
from improper installation and/or maintenance.
Local building or plumbing codes may require modifications to
the information provided. You are required to consult the local
building and plumbing codes prior to installation. If this informa-
tion is not consistent with local building or plumbing codes, the
local codes should be followed.
Need for Periodic Inspection/Maintenance: This product
must be tested periodically in compliance with local codes, but
at least once per year or more as service conditions warrant.
Replace internal components every 5 years.
Corrosive water conditions, and/or unauthorized adjustments
or repair could render the product ineffective for the service in-
tended. Regular checking and cleaning of the product's internal
components helps assure maximum life and proper product
function.
Installation Requirements
1. Install a minimum of 1" above flood level of fixture if factory
deck mounted or a minimum of 6" if general plumbing
application.
2. Install bonnet side up and allow for accessibility for testing/
service. Do not install in concealed locations or areas where
water leakage can cause damage due to normal wear of the
internal parts.
3. Do not undersize supply or oversize the valve in relation
to demand.
4. Do not install where backpressure can occur.
5. Protect assembly from freezing.
Note: Use "L" suffix for left-hand outlet.
6. The installation of a strainer ahead of the backflow preventer
is recommended to prevent fouling of the check assembly
and resultant spillage from the valve during start up and
repressuring.
Testing
For field testing procedure, send for IS-TK-DL, IS-TK-9A,
IS-TK-99E AND IS-TK-99D.
For other repair kits and service parts, send for PL-RP-BPD.
For technical assistance, contact your local Watts
representative.
Watts 008QT
",
3
8
Installations:
008QT
Watts P60
Pressure Reducing Valve
Min.
of 1"
Test
Cock
Shutoffs
Strainer
" Hose Adapter
3
4
with strainer washer
Supply Hose
008QT
6"
008QT to be
Supply Line
installed a
minimum of 6"
above the flood
rim if applied for
general plumbing
applications.
RP/IS-008QT
Watts 008QTS
3
", 1"
"
4
1
2
Solenoid Valve
Dispensing Inducers
Strainer
recommended to
prevent fouling of
the check assembly
and resultant spillage
during start up and
repressurizing.
Flood Rim Level

Publicité

loading

Sommaire des Matières pour Watts 008QT Serie

  • Page 1 ⁄ " CAUSE PROPERTY DAMAGE, PERSONAL INJURY AND/ OR DEATH. Watts is not responsible for damages resulting from improper installation and/or maintenance. Local building or plumbing codes may require modifications to the information provided. You are required to consult the local building and plumbing codes prior to installation.
  • Page 2 0.25% of lead by weight. Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment.
  • Page 3 ⁄ " UN BRIS DU PRODUIT ET ENTRAÎNER DES DOMMAGES AUX BIENS, DES BLESSURES OU LA MORT. Watts décline toute responsabilité quant aux dommages pouvant résulter d’une mauvaise installation ou d’une maintenance inadéquate. Les codes du bâtiment ou de plomberie locaux peuvent commander des modifications à...
  • Page 4 0,25 % de plomb. garantie limitée : Watts Regulator Co. (la « Société ») garantit que chacun de ses produits est exempt de vice de matériau et de fabrication dans des conditions normales d’utilisation pour une période d’un an à...

Ce manuel est également adapté pour:

Lf008qt serieLf008pc-qt