UNIVERSAL MOUNT LOW PROFILE SPEAKER AND 
CEILING MOUNT LOW PROFILE SPEAKER/STROBE
ADDITIONAL CAN/ULC LISTED PRODUCT INFORMATION IS FOUND ON PAGE 4
MODELS
SSPKCLP*................
LOW PROFILE CEILING OR WALL MOUNT SPEAKER WITHOUT STROBE
SSPK24CLP*............
LOW PROFILE CEILING MOUNT SPEAKER WITH SELECTABLE STROBE
SSPKR24C*..............
LOW PROFILE CEILING MOUNT SPEAKER WITH SELECTABLE STROBE AND RED LENS
* Includes one or more of the following designators, P (plain), A (ALERT), R (red) or W (white).
I.
INTRODUCTION
The Gentex SSPKCLP/SSPK24CLP/SSPKR24C is a high quality speaker and speaker/strobe ANSI/UL Listed for fire protective signaling systems. The high intensity strobe utilizes a Xenon flash
tube which generates a high-intensity light visible from all sides. The SSPK24CLP strobe is ANSI/UL Listed in compliance with ANSI/UL 1971, Signaling Appliances for the Hearing Impaired. The
SSPKR24 strobe is ANSI/UL Listed in compliance with ANSI/UL 1638, Visual Signaling Appliances - Private Mode Emergency and General Signaling.
II. PRODUCT INFORMATION
The SSPKCLP/SSPK24CLP/SSPKR24 Series speaker and speaker/strobe offer a choice of field selectable power taps, 1/8, 1/4, 1/2, 1, 2 and 4 Watts for either 25v or 70.7v audio amplifiers. The
SSPK24CLP speaker/strobe offers the option of a high intensity strobe which complies with ANSI/UL 1971. The SSPKR24 speaker/strobe offers the option of a high intensity strobe which complies
with ANSI/UL 1638.The frequency range of the speakers is 400-4000Hz. All devices are suitable for line supervision. Speaker includes DC blocking capacitor which allows for supervision voltage
of either polarity.
III. LOCATION
This appliance is intended for use in fire alarm systems and is to be installed in accordance with this installation manual, the recommendation of the local authorities having jurisdiction, and other
NFPA Standards that provide standards on notification appliances for protective signaling systems. The Gentex SSPKCLP/SSPK24CLP/SSPKR24 Series is intended for indoor installation only.
This appliance is not listed for outdoor or drip proof applications.
Room Spacing for Ceiling-Mounted Visible Appliances per NFPA 72, 2013 Edition
Maximum Room Size
Meters
Feet
6.10 x 6.10
20 x 20
9.14 x 9.14
30 x 30
13.4 x 13.4
44 x 44
15.2 x 15.2
50 x 50
NA = Not allowable
**Effective Intensity Requirements for Sleeping Area
Distance from Ceiling to Top of Lens
greater than or equal to 24" (610mm)
less than 24" (610mm)
Visual signal must be installed within 16 feet of the pillow when used in a sleeping area.
Visual signal must be in the direct viewing area of the occupant in order to be seen.
Visual signal cannot be seen when objects such as doors, furniture or walls block strobe light.
NOTICE: VISUAL SIGNALS FOR THE HEARING IMPAIRED ARE ONLY ONE METHOD OF ALERTING THE HEARING IMPAIRED.
VISUAL SIGNALS MAY NOT BE THE PREFERRED METHOD FOR NOTIFYING ALL HEARING IMPAIRED INDIVIDUALS.
NOTICE: THE STROBE LIGHT MUST BE SEEN BY THE SLEEPING PERSON. IF THE PERSON HAS HEAD TURNED OR OTHERWISE UNABLE TO BE ALERTED BY VISUAL, THE STROBE
WILL NOT BE EFFECTIVE.
Visual signal should NEVER be relied upon as the primary fire alert for the hearing impaired under these common sense conditions:
a. Sleeping face down on the bedding or pillow
b. Use of sleep medications of any kind
c. Use of alcoholic beverages or recreational drugs
d. Use of eye shades
e. If there are tendencies of deep sleep conditions
f.
If a fire cuts power to AC circuits, the visual signal will not operate
g. If person is not within line of sight of visual signals
Under these and other similar common situations an alternate fire alert method such as a non-hearing impaired attendant is needed. The visual signal only increases the chance
of being alerted to the presence of fire. No system of this type can fully protect the hearing impaired in case of fire.
SSPKCLP & SSPK24CLP SERIES
ANSI/UL AND CAN/ULC COMPLIANT
SSPKR24 SERIES
ANSI/UL AND CAN/ULC COMPLIANT
SSPK24CLP PRODUCT INFORMATION
Minimum Required Light Output (Effective Intensity, Cd; One Light)
Maximum Ceiling Height
10 Foot Ceiling
20 Foot Ceiling
15
30
30
45
75
75
NA
NA
Visible Notification Appliance
Intensity
110 Cd
177 Cd
30 Foot Ceiling
55
75
NA
95
550-0490
Page 1

Publicité

Table des Matières
loading

Sommaire des Matières pour Gentex SSPKCLP Serie

  • Page 1 INTRODUCTION The Gentex SSPKCLP/SSPK24CLP/SSPKR24C is a high quality speaker and speaker/strobe ANSI/UL Listed for fire protective signaling systems. The high intensity strobe utilizes a Xenon flash tube which generates a high-intensity light visible from all sides. The SSPK24CLP strobe is ANSI/UL Listed in compliance with ANSI/UL 1971, Signaling Appliances for the Hearing Impaired. The SSPKR24 strobe is ANSI/UL Listed in compliance with ANSI/UL 1638, Visual Signaling Appliances - Private Mode Emergency and General Signaling.
  • Page 2: Electrical Specifications

    PULSING SIGNALING CIRCUITS. HOWEVER, USE OF THE AVSM CONTROL MODULE IS PERMITTED TO SYNCHRONIZE THE STROBE. NOTICE: REFERENCE AVSM CONTROL MODULE MANUAL (550-0284, DATED 2-1-03) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM MANUAL CAN BE OBTAINED AT HTTP://WWW.GENTEX.COM OR CALL GENTEX CORPORATION AT 1-800-436-8391. 550-0490...
  • Page 3 5. Return to: Gentex Corporation, 10985 Chicago Dr., Zeeland MI 49464. Prior to returning, call the Gentex field service department at 1-800-436-8391 or e-mail FP_RMA@gentex.com to obtain a RMA number.
  • Page 4: Product Information

    LIMITED WARRANTY For a period of 36 months from the date of purchase or a maximum of 42 months from the date of manufacture (or as long as required by applicable law), Gentex warrants to you the original purchaser that your appliance will be free from defects in workmanship and materials under normal use and service.
  • Page 5 Cet appareil est destiné à l’intégration aux systèmes d’alarme incendie et doit être installé conformément au présent manuel, aux recommandations des autorités compétentes locales et aux normes NFPA établissant les normes pour les appareils de signalisation des systèmes de signaux de protection. Les modèles SSPKCLP/SSPK24CLP/SSPKR24 de Gentex doivent uniquement être installés à l’intérieur. Cet appareil n’est pas homologué...
  • Page 6: Renseignement Sur Le Produit Sspk24Clp

    CONSULTER LE MANUEL DUMODULE DE COMMANDE AVSM (550-0284, DATÉ DU 1ER FÉVRIER 2003) POUR LES SCHÉMAS DE CÂBLAGE DU MODULE DE SYNCHRONISATION. IL EST POSSIBLE DE SE PROCURER LE MANUEL AVSM EN ÉCRIVANT À L’ADRESSE HTTP://WWW.GENTEX.COM OU EN APPELANT GENTEX CORPORATION AU 1 800 436-8391.
  • Page 7: Installation De La Boîte Et Pose Des Fils

    5. Retourner à : Gentex Corporation, 10985 Chicago Dr., Zeeland MI 49464. Avant de retourner l’appareil, appeler le service d’assistance sur le terrain Gentex au 1 800 436-8391 ou envoyer un courriel à...
  • Page 8: Renseignements Sur Le Produit

    Si un défaut de fabrication ou de matériau entraîne la défaillance de votre appareil pendant la période de garantie, vous devez le retourner à Gentex, port payé, à l’adresse suivante : Gentex Corporation, 10985 Chicago Dr., Zeeland MI 49464. Vous devez apporter la preuve de la date d’achat de l’appareil, à la satisfaction de Gentex. Vous devez aussi fournir votre adresse pour le retour de l’appareil. Le service sous garantie peut être uniquement exécuté...

Ce manuel est également adapté pour:

Sspk24clp serieSspkr24 serie

Table des Matières