1.3 I Electricity supply connections
• Before any work inside the appliance, you must cut the electricity supply as there is a risk of
electric shock which may cause material damage, serious injury or even death.
• Poorly tightened cabling terminals can cause the cables to overheat at the terminals and create
a fire risk. Make sure that the terminal screws are fully tightened. Incorrectly tightened terminal
screws will cancel the warranty.
• Only a qualified and experienced technician is authorised to carry out cabling work within the
appliance or to replace the power cord.
• Do not disconnect the electricity supply when the appliance is running. If the electric power
supply is interrupted, wait a minute before restoring the power.
• The installer must consult the electricity provider if necessary and ensure that the equipment
is connected correctly to an electricity network with impedance under 0.095 ohm.
• The heat pump's electrical supply must be provided through a protection and circuit breaking device (not supplied)
complying with the standards and regulations in force in the country where it is installed.
• The appliance is provided for connection to a general power supply with a TT and TN.S neutral regime.
• Electrical protection: by circuit breaker (D curve, rating to be defined according to the table, see § "5.2 I Technical
data"), with a 30 mA dedicated residual-current protection system (circuit breaker or switch).
• Additional protection may be required during installation to guarantee the overvoltage category II.
• The power supply must correspond to the voltage indicated on the appliance's information plate.
• The power cord must be insulated against any cutting or hot elements that may damage or crush it.
• The appliance must be correctly connected to a suitable earth/ground circuit.
• The electrical connection lines must be fixed.
• Use the cable gland and cable clamp to pass the power cord into the appliance, see "1.3.2 Connecting the power
supply cable".
• Use the power cord (RO2V type) adapted for outdoor or buried use (or run the cable into a protection duct), see
§"1.3.1 Cable cross section" for more details.
• We recommend burying the cable at a depth of 50 cm (85 cm under a road or path) in an electrical duct (red ribbed).
• If this buried cable meets another cable or pipe (gas, water, etc.), there must be more than 20 cm between them.
1.3.1 Cable cross section
Model
Z250 MD3
Z250 MD4
Z250 MD5
Z250 MD6
* Cable cross section suitable for max. lenght 10 meters. For longer than 10 meters, consult an electrician.
9
Electricity supply
Max. current
1-phase
220-240V
/1N/ 50-60Hz
Cable diameter*
8 A
RO2V 3x2.5mm²
9 A
RO2V 3x2.5mm²
13 A
RO2V 3x2.5mm²
16 A
RO2V 3x2.5mm²
Thermal magnetic
protection
(D curve)
16 A
16 A
16 A
20 A

Publicité

loading

Ce manuel est également adapté pour:

Z250 md4Z250 md5Z250 md6