WV4460E Power Vent Water
Heater Controls
APPLICATION
The WV4460E Water Heater Control System is designed
for power vent water heater applications.
The WV4460E provides these features:
• Gas regulation and manual valve features
• Intermittent spark-to-pilot ignition
• Flame supervision using flame rectification
sensing through the spark rod. This flame sense
circuit uses patented technology to create a
robust sensing signal that is independent of AC
line polarity and appliance earth grounding.
• Water temperature sensing using solid state
sensors potted in a submersion well assembly
• Manually resettable High Temperature Cutout
(TCO)
• Induced draft blower motor control
• Draft proving switch sensing via pressure switch
• Variable resistance flammable vapor sensor with a
sensing and control algorithm to provide
automatic shutdown when hydrocarbon vapors
such as gasoline are detected
• Retains up to 10 fault code histories in non-
volatile memory (available through the
EnviraCOM™ communication port)
• Solid state setpoint adjustment over a factory
preset temperature range using a linear
potentiometer to provide high resolution
adjustment
Special control features are available to address items
such as stacking. See a Honeywell Product Specialist for
more information.
The specific application of the WV4460E System is the
responsibility of the appliance manufacturer. See the
Specifications below for temperature ranges and
regulator types. The WV4460E system refers to the
combination of the valve (VT8804A) and the electronic
control module (WT4834Q).
INSTALLATION INSTRUCTIONS
SPECIFICATIONS
IMPORTANT
WV4460E Controls provide direct replacement
only; do not substitute other models.
Body Pattern: 90 degree with 1/2 in. inlet and 1/2 in.
inverted flare outlet.
Natural gas model has right-hand threaded inverted
outlet.
LP gas model has left-hand threaded inverted outlet.
Mounting: Mounting in upright position only.
Electrical Tolerences:
Voltage Minimum: 98 Vac, 60 Hz.
Voltage Maximum: 132 Vac, 60 Hz.
Current in Running Mode: 0.1 Amps @ 120 VAC (plus
inducer motor draw)
Current in Idle Mode: 0.1 Amps @ 120 VAC
Inducer Motor drive rating: 3.5 Amps FLA and 7.0 Amps
LRA for 30,000 cycles
Capacity: See Table 1.
Conversion: Use conversion factors in Table 2 to convert
capacities for other gases.
Regulation Range (Btuh);
With 1/2 in. NPT inlet and 1/2 in. Inverted Flare Outlet:
Natural Gas:
Minimum: 30,000
Maximum: 100,000
LP Gas:
Minimum: 40,000.
Maximum: 100,000
Temperature Range:
Operating 0°F to 150°F (-18°C to 66°C)*
Storage -40°F to 175°F (-40°C to 79°C)
* Gas valve regulation range is guaranteed from 32°F to
150°F (0°C to 66°C)
Humidity:
90% Non-condensing at 95°F
Place Bar Code Here
69-1872EF-01

Publicité

Table des Matières
loading

Sommaire des Matières pour Honeywell WV4460E

  • Page 1 Storage -40°F to 175°F (-40°C to 79°C) * Gas valve regulation range is guaranteed from 32°F to The specific application of the WV4460E System is the 150°F (0°C to 66°C) responsibility of the appliance manufacturer. See the Humidity: Specifications below for temperature ranges and regulator types.
  • Page 2 , 0.64 spe- cific gravity natural gas at 0.25 kPa pressure drop). Valves are guaranteed at only 77 percent of the rating. Fig. 1. Typical capacity curve for WV4460E Family Water Heater Control System. Table 2. Gas Capacity Conversion Factor. Specific Gravity...
  • Page 3: Planning The Installation

    Proper insulation or shielding should be provided by the appliance manufacturer. Verify proper air circulation is maintained when the appliance is installed. 125 mm 100 mm M24184A Fig. 2. WV4460E dimensions in inches (mm). 69-1872EF—01...
  • Page 4 Fig. 3. Mounting the WV4460E on the water heater tank. Location The WV4460E is mounted on the outside of the water heater tank. See Fig. 3. Install Control to Water Tank 1. To install the water heater control, screw the sensor...
  • Page 5: Connect Gas Supply

    WV4460E POWER VENT WATER HEATER CONTROLS Connect Gas Supply DROP PIPED WARNING HORIZONTAL SUPPLY Fire or Explosion Hazard. Can cause severe injury, death, or property damage. Check for gas leaks with soap and water solution any time work is done on a gas system.
  • Page 6 WV4460E POWER VENT WATER HEATER CONTROLS 5. Connect the 2-wire flammable vapor sensor (TOD ON/OFF SWITCH FVS) to the Control. BLUE LED 6. Connect the Pilot Assembly lead to the Spark con- APPLY WRENCH nector. HERE WHEN CONNECTING SUPPLY LINE...
  • Page 7 WV4460E POWER VENT WATER HEATER CONTROLS Perform Gas Leak Test Gas Input and Burner Ignition Check and Adjustment 1. Check the full rate manifold pressure listed on the WARNING appliance nameplate. Water heater control full rate Fire or Explosion Hazard outlet pressure should match this rating.
  • Page 8: Sequence Of Operations

    WV4460E POWER VENT WATER HEATER CONTROLS SERVICE 4. Dusty, wet, or corrosive environment. Since these environments can cause the control to deteriorate more rapidly, the system should be checked more often. WARNING The system should be replaced if: Fire or Explosion Hazard a.
  • Page 9 WV4460E POWER VENT WATER HEATER CONTROLS TROUBLESHOOTING Troubleshooting with LED Indicator Assistance 3. Observe the ignition sequence, comparing it to the Sequence of Operations shown in Table 4. Allow the 1. Observe green LED indicator on control; check and new ignition sequence to proceed until appliance repair the system as noted in Table 5.
  • Page 10 WV4460E POWER VENT WATER HEATER CONTROLS Green LED Status Indicates Check/Repair WARNING: EXPOSION HAZARD Seven Flash, Flammable Vapor Sensor Lockout three second • Indicates gasoline vapors were detected at potentially pause explosive levels. • Verify no gasoline vapors are still present.
  • Page 11: Turning Off The Appliance

    WV4460E POWER VENT WATER HEATER CONTROLS INSTRUCTIONS TO THE STOP: READ THE HOMEOWNER WARNINGS. TURNING ON THE WARNING APPLIANCE Fire or Explosion Hazard. Can cause severe injury, death, or property damage. If the appliance does not turn on when the setpoint knob...
  • Page 12 WV4460E POWER VENT WATER HEATER CONTROLS Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North ® U.S. Registered Trademark Golden Valley, MN 55422 © 2011 Honeywell International Inc. 69-1872EF—01 M.S. 08-11 customer.honeywell.com Printed in United States...
  • Page 13: Régulateurs De Chauffe-Eau Power Vent Wv4460E

    Régulateurs de chauffe-eau Power Vent WV4460E NOTICE D'INSTALLATION APPLICATION WV4460E est constitué de la vanne (VT8804A) et du module de régulation électronique (WT4834Q). Le système de régulateur de chauffe-eau WV4460E est CARACTÉRISTIQUES conçu pour les applications avec chauffe-eau Power Vent.
  • Page 14: Pièces Accessoires (Commande Séparée)

    — Ensembles de puits : Réf. 50013231-001 : 3/4 po NPT, 1 po isolation, 3 po insertion. Capteur limiteur pour une utilisation avec les — Consulter un spécialiste des produits Honeywell pour vannes à gaz de chauffe-eau WV4460E. les autres accessoires disponibles.
  • Page 15: Préparation De L'installation

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E PRÉPARATION DE Nettoyage à l’eau ou à la vapeur L’INSTALLATION Si le régulateur se mouille, le remplacer. Si l’appareil est susceptible d’être lavé à l’eau ou à la vapeur, protéger (couvrir) le régulateur et le câblage de l’eau ou de la vapeur.
  • Page 16: Emplacement

    SE MONTE SUR LE PUITS AVERTISSEMENT MF24214A Risque de choc électrique. Fig. 3. Montage du WV4460E sur le réservoir du Peut causer des dégâts et des blessures chauffe-eau. graves, voire mortelles. Débrancher l’alimentation avant d’effectuer les connexions de câblage pour éviter les chocs électriques et les dégâts de l’équipement.
  • Page 17: Brancher L'alimentation En Gaz

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E Brancher l’alimentation en gaz COLONNE DESCENDANTE ALIMENTATION AVERTISSEMENT HORIZONTAL EN GAZ (TUYAU) Risque d’incendie ou d’explosion. Peut causer des dégâts et des blessures graves, voire mortelles. Vérifier l’absence de fuites de gaz avec une solution savonneuse à...
  • Page 18: Remplissage Du Réservoir

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E 6. Brancher le fil de la veilleuse au connecteur INTERRUPTEUR d’étincelle MARCHE/ARRÊT DEL VERTE METTRE LA CONNECTEUR D’ÉTINCELLE CLÉ ICI POUR (VERS VEILLEUSE Q3451J) CONNECTER LA CANALISATION D’ARRIVÉE CONNECTEUR ENVIRACOM À 3 BROCHES CONNECTEUR...
  • Page 19: Test De Fuite De Gaz

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E Considérer l’âge et la santé de tous ceux qui du relevé du compteur). Convertir le débit en Btuh entreront en contact avec l’eau chaude. comme décrit dans le formulaire 70-2602, manuel des régulateurs à gaz, et comparer la valeur d’entrée Test de fuite de gaz nominale en Btuh à...
  • Page 20: Entretien

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E ENTRETIEN 4. Environnement poussiéreux, mouillés ou corrosifs. Ces environnements pouvant causer une détérioration plus rapide du régulateur, le système doit être vérifié plus souvent. AVERTISSEMENT Le système doit être remplacé dans les cas suivants : Risque d’incendie ou d’explosion.
  • Page 21: Dépannage

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E Séquence Mode Description La température atteint le point de consigne L’appel de chauffage est satisfait (la température atteint le point de consigne). Désactivation des vannes de gaz Les vannes de gaz sont désactivées. principale et de veilleuse Surveillance de flamme La flamme est contrôlée jusqu’à...
  • Page 22 RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E Statut de la DEL verte Indique Vérification/réparation • Vérifier la ventilation pour s’assurer que le pressostat ne s’ouvre Six séquences de deux Verrouillage de premier pas momentanément pendant que l’appareil chauffe. clignotements, pause niveau – Source •...
  • Page 23 RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E VÉRIFIER : METTRE L’INTERRUPTEUR SUR MARCHE, TOURNER LE BOUTON DE LA TEMPÉRATURE DU RÉSERVOIR DOIT ÊTRE ÉGALE RÉGLAGE SUR CHAUD; L’INDUCTEUR AU/PROCHE DU POINT DE RÉGLAGE DOIT DÉMARRER CÂBLAGE DE L’ALIMENTATION TENSION SECTEUR CÂBLAGE DE L’INDUCTEUR, RETOUR L2 INCLUS CAPTEUR DE TEMPÉRATURE ET CAPTEUR DE VAPEURS...
  • Page 24: Instructions Au Propriétaire

    RÉGULATEURS DE CHAUFFE-EAU POWER VENT WV4460E INSTRUCTIONS AU STOP! LIRE LES PROPRIÉTAIRE AVERTISSEMENTS. MISE EN MARCHE DE AVERTISSEMENT L’APPAREIL Risque d’incendie ou d’explosion. Peut causer des dégâts et des blessures graves, voire mortelles. Si l’appareil ne se met pas en marche quand le bouton Respecter ces avertissements avec précision :...

Table des Matières