ST9120B,U
Universal Electronic Fan Timers
APPLICATION
The ST9120B,U Universal Electronic Fan Timers
integrate control of all combustion blower and circulating
fan operations in a gas warm air appliance. This control
is the central wiring point for most of the electrical
components in the furnace. The basic purposes of the
ST9120B,U are to monitor the thermostat for heat, cool
and fan demands, run the induced draft blower motor
and run a circulating fan (up to two speeds) as required.
The ST9120B,U also monitors limit switch strings and
energizes separate ignition control systems through
pressure switches. The ST9120B,U can replace any
ST9101, ST9120, ST9141 or ST9160 listed in Table 3
below. The ST9120B,U features a field-adjustable heat
fan-on delay, a field-adjustable heat fan-off delay, a field-
adjustable cool fan-on delay and a field-adjustable cool
fan-off delay.
Electronic air cleaner (EAC) and humidifier (HUM)
convenience terminal connections and continuous low
speed indoor air circulation are provided.
SPECIFICATIONS
Electrical Ratings:
Power Voltage Requirements: 18 to 30 VAC, 50/60 Hz.
Contact Ratings:
Combustion Blower:
1.5A full load, 10A locked rotor at 115 VAC.
0.75A full load, 5A locked rotor at 230 VAC.
(Reduce full load rating by humidifier [HUM] load.)
Circulating Fan:
Heat-Cool speed:
15A full load, 30A locked rotor at 115 VAC.
7.5A full load, 15A locked rotor at 230 VAC.
(Reduce full load rating by electronic air cleaner [EAC]
load.)
Continuous speed (optional):
8A full load, 16A locked rotor at 115 VAC.
4A full load, 8A locked rotor at 230 VAC.
EAC and HUM:
0.8A maximum combined load at 115 VAC
0.4A maximum combined load at 230 VAC
Thermostat W Load: 100mA at 24 VAC, plus ignition sys-
tem load.
Thermostat G, Y, Primary Limit, Burner Limit, Pressure
Switch Load: 22mA at 24 VAC load/cleaning current.
INSTALLATION INSTRUCTIONS
On/Off Delay Settings:
NOTE: Timing is derived from 24 VAC supply frequency
and is valid for 60Hz. At 50 Hz, the timings are
lengthened 20%.
Heat Speed:
Delay On: Field-adjustable, 30 or 60 seconds. Delay
timing starts when gas valve is energized.
Delay Off: Field-adjustable, 60, 120, 150 or 180 sec-
onds. Delay timing starts when gas valve is de-
energized.
Cool Speed:
Delay On: Field Adjustable, 4 or 30 seconds.
Delay Off: Field Adjustable, 30 or 60 seconds.
Timing Tolerance: Larger of ±2% or ±2 seconds.
Post Purge Timing:
5 seconds.
Environmental Ratings:
Temperature: -40°F (-40°C) to +175°F (+79°C).
Humidity: 5 to 95 percent, noncondensing.
Approvals:
Underwriters Laboratories Inc.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings and specifications given in the
instructions and on the product to make sure the
product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before wiring to prevent
electrical shock or equipment damage. More than
one disconnection can be required.
69-2252EF—07

Publicité

loading

Sommaire des Matières pour Honeywell ST9120B

  • Page 1 The basic purposes of the timing starts when gas valve is energized. ST9120B,U are to monitor the thermostat for heat, cool Delay Off: Field-adjustable, 60, 120, 150 or 180 sec- and fan demands, run the induced draft blower motor onds.
  • Page 2 VAC HOT legs connected to X terminals at each ing adapter directly to the open 6-pin connector on ST9120B,U unit must be in the same phase relative to the the new ST9120B,U control board. 24 VAC common ground). If the transformers are phased 4.
  • Page 3 * ACC terminal is used in ST9101 systems, which use the same fan speed for both heating and cooling. In order to use the ST9120B,U to replace ST9101 devices in this type of system, the fan connection that originally was connected to ACC on the ST9101 needs to be connected to both heat and cool connections on the ST9120B,U.
  • Page 4 ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS Table 2. LED Diagnostic Troubleshooting Codes. No. of flashes Condition dim/on (heartbeat) Device works correctly. Limit switch (ST9120) or burner limit switch (ST9141) is open. Primary limit switch (ST9141) is open. Pressure switch is improperly closed or pressure switch open when inducer blower has been running for >30 sec.
  • Page 5 ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS Table 3. Recommended Default Dip Switch Settings. (Continued) Legacy Timing New ST9120B,U Heat Heat Cool Cool Replaced Heat On Heat Off Cool On Cool Off Control Model Original OEM Number Appliance ST9150B2000 ST9150B2018 ST9150B2026 Ducane...
  • Page 6 CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED. DENOTES LINE VOLTAGE WIRING CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED. DENOTES LOW VOLTAGE WIRING M27704 Fig. 1. Typical ST9120B,U wiring connections in ST9120 system with S8600 Intermittent Pilot Ignition Control. 69-2252EF—07...
  • Page 7 CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED. DENOTES LINE VOLTAGE WIRING DENOTES LOW VOLTAGE WIRING CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED. M27705 Fig. 2. Typical ST9120B,U wiring connections in ST9120 system with SV9500/SV9501 SmartValve™ Control. 69-2252EF—07...
  • Page 8 CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED. DENOTES LINE VOLTAGE WIRING DENOTES LOW VOLTAGE WIRING CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED. M27722 Fig. 4. Typical ST9120B,U wiring connections in ST9141 system with SV9500/SV9501 SmartValve™ Control. 69-2252EF—07...
  • Page 9 JUMPER PLUG MUST BE ATTACHED TO J1 CONNECTOR. CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED. CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED M16880 Fig. 5. Typical ST9120B,U wiring connections in ST9160 system with SV9510/SV9520 SmartValve™ Control. 69-2252EF—07...
  • Page 10 DENOTES LOW VOLTAGE WIRING FOR 115 VAC / 50, 60 HZ INSTALLATIONS, THERE MUST BE 115 VAC CONNECTED TO L1 (HOT) ON ST9120U, ST9120B. FOR 230 VAC / 60 HZ INSTALLATIONS, THERE MUST BE 115 VAC BETWEEN L1 (HOT) AND APPLIANCE CHASSIS.
  • Page 11 ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS Table 4. ST9101 Wire Harness Adapter (HPN 50011959-001) Connections. Connector/Wire Identification Reference Connect To… 9 pin 9 pin system connector in ST9101 appliance 6 pin J1 connector at ST9120B,U White E13/E15/E18/E20/E23/E26 (Neutral) at ST9120B,U White...
  • Page 12 ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS Table 6. ST9160 Jumper Plug (HPN 50034963-001) Connections. Connector/Wire Identification Connect To… 6 pin J1 connector at ST9120B,U NOT CONNECTED NOT CONNECTED NOT CONNECTED NOT CONNECTED 50034963 M27729 Fig. 9. ST9160 jumper plug 50034963 schematic.
  • Page 13 1. Circulating fan low speed is energized when there is no call for heat, cool, connected. or fan. (Optional connection to circulating 2. If fan operation is required by a call for heat, cool, or fan, ST9120B,U fan low speed tap) switches circulating fan to appropriate speed. Electronic air cleaner is connected.
  • Page 14 (Optional connection to or fan. circulating fan low speed tap) 2. If fan operation is required by a call for heat, cool, or fan, ST9120B,U switches circulating fan to appropriate speed. Electronic air cleaner is connected. 1. In two-speed systems, the electronic air cleaner is energized when the (Optional connection to line voltage heat or cool speed of the circulating fan is energized.
  • Page 15 (Optional connection to or fan. circulating fan low speed tap) 2. If fan operation is required by a call for heat, cool, or fan, ST9120B,U switches circulating fan to appropriate speed. Electronic air cleaner is connected. 1. In two-speed systems, the electronic air cleaner is energized when the (Optional connection to line voltage heat or cool speed of the circulating fan is energized.
  • Page 16 ST9120B,U UNIVERSAL ELECTRONIC FAN TIMERS Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive ® U.S. Registered Trademark Toronto, Ontario M1V 4Z9 © 2010 Honeywell International Inc. 69-2252EF—07 C.H.
  • Page 17 à 24 V c.a. et une fréquence de pressostats. Le ST9120B,U peut remplacer tous les 60 Hz. À 50 Hz, la temporisation est pro- ST9101, ST9120, ST9141 ou ST9160 indiqués au Table longée de 20 %.
  • Page 18 à l’application prévue. 3. L’installateur doit être un technicien d’expérience Pour passer en mode de pairage, les deux ST9120B,U ayant reçu la formation pertinente. doivent partager une même mise à la terre 24 V c.a., ils 4.
  • Page 19 ST9120B,U. ** La borne TWIN sert à relier entre eux deux régulateurs ST9120B,U pour qu’ils fassent fonctionner les sorties de ven- tilateur simultanément. La fonction de pairage du nouveau ST9120B,U ne peut être employée avec les anciens régu- lateurs.
  • Page 20 étiqueter chaque fil avant de le et le raccorder directement au panneau de com- débrancher de son panneau de commande mande du nouveau ST9120B,U avant de retirer le d’origine. régulateur existant. Consulter le Table 1 pour déter- 2.
  • Page 21 MINUTERIES DE VENTILATEUR UNIVERSELLES ET ÉLECTRONIQUES ST9120B,U Tableau 3. Réglage recommandé des commutateurs DIP. (Continued) Temporisation de l’ancien régulateur Nouveau ST9120B,U Numéro de Chaleur Chaleur Refr. Refr. Chaleur Refroid Refroid modèle de Fabricant marche arrêt marche arrêt marche Chaleur arrêt marche arrêt...
  • Page 22 MINUTERIES DE VENTILATEUR UNIVERSELLES ET ÉLECTRONIQUES ST9120B,U VENTILATEUR FILTRE DE TIRAGE À AIR HUMIDIFICATEUR VERS L’ALIMENTATION 115/230 V c.a. FUSIBLE L1 (SOUS TENSION) L2 (N) CONDENSATEUR VENTILATEUR DE DÉMARRAGE ÉTAT TEMPORISATION LIMITEUR DE FIN DE 115/230 V c.a. PAIRAGE TRANSFORMATEUR COURSE 24 V c.a.
  • Page 23 MINUTERIES DE VENTILATEUR UNIVERSELLES ET ÉLECTRONIQUES ST9120B,U VENTILATEUR DE TIRAGE HUMIDIFICATEUR FILTRE À AIR VERS L’ALIMENTATION 115/230 V c.a. FUSIBLE L1 (SOUS TENSION) L2 (N) CONDENSATEUR VENTILATEUR DE DÉMARRAGE COMMUN 24 VOLTS 24 VOLTS SOUS TENSION ÉTAT SORTIE TVÉ TEMPORISATION...
  • Page 24 À RACCORDER SEULEMENT S’IL Y A UNE FONCTION DE VITESSE CONTINUE UTILISÉE RACCORDEMENT TENSION SECTEUR RACCORDEMENT BASSE TENSION À RACCORDER SEULEMENT SI LA FONCTION DE VITESSE CONTINUE N’EST PAS UTILISÉE MF27722 Fig. 4. Schéma de raccordement type du ST9120B,U dans un système ST9141 avec régulateur SmartValve SV9500/SV9501. 69-2252EF—07...
  • Page 25 À RACCORDER SEULEMENT S'IL Y A UNE FONCTION DE VITESSE CONTINUE UTILISÉE. À RACCORDER SEULEMENT SI LA FONCTION DE VITESSE CONTINUE N’EST PAS UTILISÉE. MF16880 Fig. 5. Schéma de raccordement type du ST9120B,U dans un système ST9160 avec régulateur SmartValve SV9510/SV9520.
  • Page 26 À RACCORDER SEULEMENT S’IL Y A UNE FONCTION DE VITESSE CONTINUE UTILISÉE. À RACCORDER SEULEMENT SI LA FONCTION DE VITESSE CONTINUE N’EST PAS UTILISÉE. Fig. 6. Schéma de raccordement type du ST9120B,U dans un système ST9160 avec régulateur SmartValve SV9540/SV9640.
  • Page 27 Blanc E13/E15/E18/E20/E23/E26 (Neutre) au ST9120B,U Blanc E13/E15/E18/E20/E23/E26 (Neutre) au ST9120B,U Noir E12/E14 (L1 phase) au ST9120B,U Bleu VENTILATEUR E17 (sortie du ventilateur de tirage) au ST9120B,U DE TIRAGE L2 BLANC L2 BLANC ENTRAÎNEMENT PS/MV ORANGE LIMITEUR ROUGE LIMITEUR ROUGE L1 NOIR NON RACCORDÉ...
  • Page 28 MINUTERIES DE VENTILATEUR UNIVERSELLES ET ÉLECTRONIQUES ST9120B,U Tableau 6. Connexions de la prise du cavalier du ST9160 (no de pièce 50034963-001). Connecteur/Couleur du fil Raccordé à... 6 broches Connecteur J1 au ST9120B,U NON RACCORDÉ NON RACCORDÉ NON RACCORDÉ NON RACCORDÉ...
  • Page 29 2. S’il y a commande de chauffage, de refroidissement ou de ventilation, le ventilateur de circulation ST9120B,U fait fonctionner le ventilateur de circulation d’air à la vitesse d’air.) appropriée. Un filtre à air électronique est 1.
  • Page 30 (Raccordement facultatif à la borne ventilation. de basse vitesse du ventilateur de 2. S’il y a commande de chauffage, de refroidissement ou de ventilation, le circulation d’air.) ST9120B,U fait fonctionner le ventilateur de circulation d’air à la vitesse appropriée. 69-2252EF—07...
  • Page 31 2. S’il y a commande de chauffage, de refroidissement ou de ventilation, le ventilateur de circulation d’air.) ST9120B,U fait fonctionner le ventilateur de circulation d’air à la vitesse appropriée. Un filtre à air électronique est 1.
  • Page 32 MINUTERIES DE VENTILATEUR UNIVERSELLES ET ÉLECTRONIQUES ST9120B,U Tableau 10. Conditions d’erreur. Condition d’erreur Fonctionnement Limiteur du brûleur ouvert 1. Le ventilateur de tirage est sous tension. (ST9141) 2. Si la borne Y est sous tension, le ventilateur de circulation devrait fonction- Limiteur ouvert (ST9120) ner au régime de refroidissement;...

Ce manuel est également adapté pour:

St9120u