R7120M 7800 SERIES
Relay Modules
APPLICATION
The R7120M is a microprocessor-based functional plug in
replacement for the Fireye M Series system utilizing the
existing wiring subbase. The R7120M is an integrated control
for automatically fired gas, oil, or combination fuel single
burner, on/off applications. The R7120M system consists of a
relay module, amplifier, and purge card. Options include
keyboard display module (KDM), Data ControlBus™ Module,
remote display mounting. See the Honeywell Primary Control
Cross Reference (form number 95-6855 available on web site
www.customer.honeywell.com) for correct parts and feature
selection options.
Functions provided by the R7120M include automatic burner
sequencing, flame supervision, system status indication,
system or self-diagnostics and troubleshooting.
The R7120 adds a blinking fault code function to the POWER
LED on Alarm shutdown, and programmable postpurge using
the S7800A1142 Keyboard Display Module (KDM).
The R7120M1001 has intermittent pilot for Fireye M1, M2 and
M3 controller. The R7120M1019 offers interrupted pilot for
Fireye M5 controller.
This document provides installation and system checkout
instructions. Other applicable publications are:
Publication
No.
65-0288
S7800A1142 Keyboard Display Module
Product Data
65-0091
S7810A Data ControlBus Module™ Product
Data
65-0095
S7820 Remote Reset Module Product Data
65-0097
221729C Dust Cover Installation
Instructions
65-0109
R7824, R7847, R7848, R7849, R7851,
R7852, R7861, R7886 Flame Amplifiers for
the 7800 Series Product Data
65-0131
221818A Extension Cable Assembly
Product Data
65-0249
S7810M ModBUS Module
Product
INSTALLATION INSTRUCTIONS
SPECIFICATIONS
Electrical Ratings (See Table 3):
Voltage and Frequency:
R7120M: 120 Vac (+10/-15%), 50/60 Hz (± 10%).
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A Fast Blow, type SC or
equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to 60°C).
Storage: -40°F to 150°F (-40°C to 66°C).
Humidity: 85% relative humidity continuous, noncondensing.
Vibration: 0.5G environment.
Approvals:
cULus component listed: File No. MP268, Guide No.
MCCZ.
Federal Communications Commission: Part 15, Class B,
Emissions.
Required Components for operation (order separately):
Choose based on configuration of the Fireye Control being
replaced (see form 95-6855 for assistance):
Purge Timer
Flame Amplifier
Flame Detector
Provided parts:
1 adapter plate
2 screws (1/4 in. long 8-32 flathead Phillips)
1 leadwire for grounding
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and marked
on the product to make sure the product is suitable for
the application.
3. Installer must be a trained, experienced, flame
safeguard service technician.
66-1193EF-01

Publicité

Table des Matières
loading

Sommaire des Matières pour Honeywell R7120M 7800 Serie

  • Page 1 Fusing Total Connected Load: 15A Fast Blow, type SC or keyboard display module (KDM), Data ControlBus™ Module, equivalent. remote display mounting. See the Honeywell Primary Control Cross Reference (form number 95-6855 available on web site Environmental Ratings: www.customer.honeywell.com) for correct parts and feature Ambient Temperature: selection options.
  • Page 2 R7120M 7800 SERIES RELAY MODULES Location 4. After installation is complete, perform the system check- out provided in these instructions. Humidity WARNING Install the relay module where the relative humidity never reaches the saturation point. The relay module is designed to Fire or Explosion Hazard.
  • Page 3 R7120M 7800 SERIES RELAY MODULES NOTE: A 13 Vdc power supply must be used any time more 10. Be sure loads do not exceed the terminal ratings. Refer than one KDM is used. to the label on the R7120M or to the terminal ratings in Table 3 9.
  • Page 4 R7120M 7800 SERIES RELAY MODULES OPERATION FUEL CONTROL LIMITS INTERLOCKS FLAME DETECTOR BURNER MOTOR CONTACTOR PILOT VALVE MAIN VALVE ALARM AIRFLOW SWITCH IGNITION BURNER CONTROL 120 VAC INITIATE PFEP (INITIAL 10 SEC. POWERUP TIMED (4 SEC. IF ONLY) STANDBY PREPURGE JR1 CLIPPED MFEP POSTPURGE...
  • Page 5 R7120M 7800 SERIES RELAY MODULES Table 2. Recommended Grounding Practices. Ground Type Recommended Practice Earth ground (subbase and relay 1. Use to provide a connection between the subbase and the control panel of the module). equipment. Earth ground must be capable of conducting enough current to blow the 15A, type SC, fast blow fuse (or breaker) in the event of an internal short circuit.
  • Page 6: General Instructions

    R7120M 7800 SERIES RELAY MODULES Table 5. Composition of each Combination. 4.5A ignition 50 VA Pilot Duty plus 180 VA Ignition plus 2A Pilot Duty 65 VA Pilot Duty plus 4.5A ignition. motor valves with: motor valves with: 660 VA inrush, 3850 VA inrush, 360 VA open, 700 VA open,...
  • Page 7 R7120M 7800 SERIES RELAY MODULES WIRING SUBBASE ADAPTER PLATE RUN/TEST SWITCH RELAY MODULE CONFIGURATION JUMPERS PURGE TIMER SEQUENCE STATUS LED PANEL POWE R RESET PILOT BUTTON FLAM E MAIN ALAR M KEYBOARD CAPTIVE DISPLAY RESE T MOUNTING MODULE SCREW (OPTIONAL) FLAME AMPLIFIER BA CK...
  • Page 8: Sequence Of Operation

    R7120M 7800 SERIES RELAY MODULES e. Internal system fault occurred. ±10% during any part of the operating sequence. The Purge card is removed. INITIATE sequence lasts for ten seconds unless the voltage or g. Purge card is bad. frequency tolerances are not met. When not met, a hold 5.
  • Page 9: Settings And Adjustments

    R7120M 7800 SERIES RELAY MODULES SERVICE NOTE: Clipping and removing a site-configurable jumper enhances the level of safety. The relay module is now in RUN and remains in RUN until the controller input, terminal 6, opens, indicating that the demand IMPORTANT is satisfied or a limit has opened.
  • Page 10 R7120M 7800 SERIES RELAY MODULES Table 7. Blinking Fault Codes and Recommended Troubleshooting. Fault Code System Failure Recommended Troubleshooting Code 1-1 Low AC Line detected. 1. Check the relay module and display module connections. *Low AC Line 2. Reset and sequence the Relay Module. Voltage* 3.
  • Page 11: System Checkout

    R7120M 7800 SERIES RELAY MODULES Table 7. Blinking Fault Codes and Recommended Troubleshooting. (Continued) Fault Code System Failure Recommended Troubleshooting Code 4-1 No purge card or the 1. Make sure the purge card is seated properly. *Purge Card purge card timing has 2.
  • Page 12 R7120M 7800 SERIES RELAY MODULES Equipment Recommended Make sure all manual fuel shutoff valves are closed before starting initial lightoff check and Pilot Turndown tests. S7800A Keyboard Display Module Do not put the system in service until you have satisfactorily Volt-ohmmeter (1M ohm/volt minimum sensitivity) with: 0-300 completed all applicable tests in this section and any others Vac capability.
  • Page 13 R7120M 7800 SERIES RELAY MODULES 4. Let the sequence advance to PILOT IGN (status is dis- c. Check for adequate low fire fuel flow. played on the Keyboard Display Module, if used), d. Check for proper gas supply pressure. PILOT LED turns on, ignition spark should occur and e.
  • Page 14 R7120M 7800 SERIES RELAY MODULES 10. If the first stage burner flame is not established within If using AMPLI-CHECK™ or self-checking amplifier and four seconds, or within the normal lightoff time specified 1M ohm/voltmeter, the flame signal fluctuates every time the by the equipment manufacturer, close the manual fuel amplifier does a self-check or a shutter check.
  • Page 15 R7120M 7800 SERIES RELAY MODULES Hot Refractory Hold-in Test (Rectifying 12. Close the master switch to recycle the burner and stop the sequence in the PILOT period by using the Photocell, Infrared Detectors, Ultraviolet Run/Test Switch. 13. Increase the pilot flame size by increasing its fuel flow Detectors) until a smooth main flame is accomplished.
  • Page 16 0.5 Vdc. c. Safety shutdown occurs. 2. Failure to ignite pilot. NOTE: The Honeywell Q624A and Q652B Solid State Spark a. Close pilot and main fuel manual shutoff valve(s). Generators prevent detection of ignition spark when b.
  • Page 17 Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35 Dynamic Drive ® U.S. Registered Trademark Toronto, Ontario M1V 4Z9 © 2010 Honeywell International Inc. 66-1193EF—01 M.S. Rev. 11-10 customer.honeywell.com Printed in U.S.A.
  • Page 18 ControlBus™ et un système d'affichage à distance. Voir le 65-0288 Données techniques du module afficheur et formulaire de correspondance des régulateurs primaires clavier S7800A1142 Honeywell (réf. 95-6855, disponible sur le site Web 65-0091 Données techniques du module Data www.customer.honeywell.com) pour les pièces correctes et la ControlBus™ S7810A sélection des caractéristiques.
  • Page 19: Caractéristiques

    MODULES DE RELAIS R7120M SÉRIE 7800 CARACTÉRISTIQUES AVERTISSEMENT Risque de choc électrique. Caractéristiques électriques (voir tableau 3) : Peut causer des dégâts et des blessures graves, Tension et fréquence : voire mortelles. R7120M : 120 V c.a. (+10/-15 %), 50/60 Hz (± 10 %). Débrancher l'alimentation avant de commencer Dissipation d'énergie : 10 W maximum.
  • Page 20: Humidité Sur Le Site

    MODULES DE RELAIS R7120M SÉRIE 7800 Humidité sur le site 4. Tout le câblage doit être conforme aux codes d'électri- cité, aux lois et aux règlements locaux en vigueur. Le Installer le module de relais à un endroit où l'humidité relative câblage doit être conforme au câblage NEC Classe 1 n'atteint jamais le point de saturation.
  • Page 21 MODULES DE RELAIS R7120M SÉRIE 7800 Tableau 9. Dimensions et références des fils recommandées. Application Dimensions des fils recommandées Numéros de pièces recommandées Bornes de tension secteur. Conducteur en cuivre de 14, 16 ou 18 AWG, isolation TTW60C, THW75C, THHN90C. 600 V, résistant à...
  • Page 22 MODULES DE RELAIS R7120M SÉRIE 7800 LIMITEURS COMMANDE DE VERROUILLAGES FONCTIONNEMENT DE COMBUSTIBLE DÉTECTEUR DE FLAMME MOTEUR DE BRÛLEUR OU CONTACTEUR VANNE DE VEILLEUSE VANNE PRINCIPALE ALARME INTERRUPTEUR ALLUMAGE DE DÉBIT D’AIR RÉGULATEUR DE BRÛLEUR 120 V c.a. TEMPS DE PÉRIODE SÉCURITÉ...
  • Page 23 MODULES DE RELAIS R7120M SÉRIE 7800 Tableau 10. Pratiques de mise à la masse recommandées. Type de masse Pratique recommandée Prise de terre (plaque de 1. Utiliser pour fournir une connexion entre la plaque de raccordement et le tableau de raccordement et module de relais).
  • Page 24: Instructions Générales

    MODULES DE RELAIS R7120M SÉRIE 7800 Tableau 13. Composition of each Combination. 4,5 A allumage 50 VA Circuit de 180 VA Allumage plus 2A Circuit de commande 65 VA Circuit de commande plus 4,5 A vannes de moteur avec : commande plus vannes allumage.
  • Page 25: Paramétrage Du Post-Balayage (Si Requis)

    MODULES DE RELAIS R7120M SÉRIE 7800 Paramétrage du post-balayage (si requis) Un module afficheur à clavier (KDM) S7800A1142 est requis pour paramétrer le temporisateur de prébalayage R7120 et doit être acheté séparément. Suivre les instructions fournies dans la feuille d'instructions de l'afficheur (référence 65-0288). PLAQUE DE RACCORDEMENT PLAQUE D’ADAPTATEUR INTERRUPTEUR DE...
  • Page 26: Séquence De Coupure De Sécurité

    MODULES DE RELAIS R7120M SÉRIE 7800 Séquence de coupure de sécurité : 2. PÉRIODE DE VEILLE a. L'option de verrouillage du débit d'air est activée 1. Une coupure de sécurité intervenant durant le démar- (JR3 coupé) et l'interrupteur de débit d'air ne se rage ou la veille verrouillera le R7120 (en l'empêchant ferme pas après 10 secondes ou dans le temps de démarrer) et sera indiqué...
  • Page 27: Réglages Et Ajustements

    MODULES DE RELAIS R7120M SÉRIE 7800 le cavalier JR2 est coupé) au bout de 0,8 ou 3 La séquence DÉMARRAGE impose un délai au démarreur du secondes, en fonction du temps de réponse en cas moteur du brûleur en l'empêchant de se mettre sous tension d'extinction de la flamme (FFRT) de l'amplificateur.
  • Page 28 MODULES DE RELAIS R7120M SÉRIE 7800 Tableau 14. Options de cavaliers configurables sur site. Numéro CAVALIERS DE CONFIGURATION DISPONIBLES INTERRUPTEUR MARCHE/TEST (EC7895C; RM7895C,D; RM7896C,D) cavalier Description Intact Coupé Période d'établissement 4 secondes de la veilleuse (PFEP) secondes Action d'échec de Remise en Verrouillage flamme...
  • Page 29 MODULES DE RELAIS R7120M SÉRIE 7800 Tableau 15. Codes de panne clignotants et dépannage recommandé Code de panne Panne du système Dépannage recommandé Code 2-2 Période sans flamme 1. Mesurer le signal de flamme. S'il en existe un, vérifier qu'il est conforme aux *Signal de présente à...
  • Page 30 MODULES DE RELAIS R7120M SÉRIE 7800 Tableau 15. Codes de panne clignotants et dépannage recommandé Code de panne Panne du système Dépannage recommandé Code 4-1 Pas de carte de 1. S'assurer que la carte de balayage est bien installée. *Problème de balayage ou la 2.
  • Page 31: Vérification Du Système

    MODULES DE RELAIS R7120M SÉRIE 7800 VÉRIFICATION DU SYSTÈME Ne pas mettre le système en service tant que tous les tests applicables de cette section n'ont pas été terminés de façon satisfaisante, ainsi que tout autre test recommandé par le fabricant de l'équipement d'origine.
  • Page 32: Inspection Préliminaire

    MODULES DE RELAIS R7120M SÉRIE 7800 Inspection préliminaire mage doit avoir lieu et la veilleuse s'allumer. Si la veilleuse s'allume, la DEL Flamme est activée. Passer à Effectuer les inspections suivantes pour éviter les problèmes l'étape 7. communs. S'assurer que : 5.
  • Page 33 MODULES DE RELAIS R7120M SÉRIE 7800 12. Ouvrir la ou les vannes de coupure de combustible manu- REMARQUE : Les limiteurs de faible pression de carburant elles en douceur et retester l'allumage. (La première reten- peuvent être ouverts, le cas échéant. Si c'est le tative peut avoir été...
  • Page 34: Test De Réglage Minimum De La Veilleuse (Toutes Installations Avec Veilleuse)

    MODULES DE RELAIS R7120M SÉRIE 7800 18. Si une deuxième étape est utilisée, s'assurer que la ou 3. Brancher un manomètre (ou une jauge de pression) les vannes de combustible automatiques de deuxième pour mesurer la pression de gaz de veilleuse durant le étape sont ouvertes.
  • Page 35: Test D'interférence De L'allumage (Toutes Électrodes De Flamme)

    MODULES DE RELAIS R7120M SÉRIE 7800 Test de saturation de l'élément réfractaire les vannes de coupure de combustible principales ma- nuelles et ouvrir l'interrupteur principal. Si l'allumage ne chaud (tous les détecteurs à infrarouge) se fait pas en douceur, la taille de la flamme de veilleuse est trop petite.
  • Page 36: Test De Réponse De L'étincelle D'allumage (Tous Les Détecteurs Ultraviolets)

    Effectuer ces tests à la fin de la vérification, une fois que tous REMARQUE : Les générateurs d'étincelles à semi-conduc- les autres tests ont été effectués. Le cas échéant, l'alarme teur Q624A et Q652B d'Honeywell empêchent externe doit se mettre en route. Appuyer sur le bouton la détection de l'étincelle d'allumage lorsqu'ils poussoir de Réarmement sur le module de relais pour...
  • Page 37 MODULES DE RELAIS R7120M SÉRIE 7800 c. La ou les vannes automatiques de la veilleuse c. Démarrer le système. Le démarrage doit s'effectuer doivent être sous tension mais la veilleuse ne peut normalement et le brûleur principal doit s'allumer pas s'allumer. normalement.
  • Page 38 MODULES DE RELAIS R7120M SÉRIE 7800 66-1193EF—01...
  • Page 39 MODULES DE RELAIS R7120M SÉRIE 7800 66-1193EF—01...
  • Page 40 Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35, Dynamic Drive ® Marque de commerce déposée aux É.-U. © 2010 Honeywell International Inc. Toronto (Ontario) M1V 4Z9 Tous droits réservés 66-1193EF—01 M.S. Rev. 11-10 customer.honeywell.com...

Table des Matières