Connecting Power - Siemens SITRANS FUS1010 Guide Rapide

Masquer les pouces Voir aussi pour SITRANS FUS1010:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Quick Start Guide
WARNING: Turn off main power before installing AC connections to the Flow Display Computer. Contact with exposed wiring
!
may lead to fire, electric shock, or serious personal injury.
Open the Flow Display Computer top cover by releasing the cover latch.
Unscrew the two power supply access cover fasteners and remove access cover.
Locate power supply connector J10. Using a flat blade screwdriver, remove plug P10 from connector J10. Set aside.
NOTE: Agency approved units will be fused with F1 and non-agency approved units will have an On/Off breaker switch.
Power Supply Label
Siemens
Power Supply
Access Cover
Pull the desired length of input power wires through a cable gland and into Flow Display Computer case before wiring
connector.
Wire input power connector P10 for AC or DC power depending on power supply provided. Insert wires into wire entry
holes and secure by tightening wire clamp screws (see figure above). NOTE: Power Supply connector wires should be
stripped AWG 12 -18 stranded wire or solid conductors.
Plug input power plug P10 into connector J10 and secure using two captive connector mounting screws.
Replace access cover. Make sure the Keypad Enable switch is in the "Enable" position (see below).
Caution: Improper connections will damage power supply. Turn power switch to ON (if so equipped). Connect the
power cables to the appropriate power source (100-250 VAC @ 50/60 Hz or 9-36 VDC). Close top cover.
Within 10 seconds of power-up the Flow Display Computer main display will become active and a typical Siemens
graphic will appear. The screen also identifies the software version of the unit as shown below.
Press the <MENU> key and the Main Menu will appear. (Note: Language selection not on Version 3 op system.)
Siemens
2 Channel [1]
Select Meter Type
Meter Type
Meter Facilities
Language
ss

Connecting Power

Fuse F1
J10
Color Codes
Hot Neu GND
USA BK
EU
BR
Input Power Plug (P10) Wiring
Channel 1
>2 Channel Flow
Dual Path Flow
Ch 1 + 2 Flow
Ch 1 - 2 Flow
2
1
3
P10
AC
NEU
GND
HOT
DC
+
-
GND
Stripped Wire
WH GRN
BL Y/GRN
Ver. 5.03.00G
1
2
3
Wire
Clamp
Connector
Screws
Mounting
Screws
Software
Version
(x.xx.xx)