Preliminary Setup Procedures; Mounting The Flowmeter; Figure 1 Pipe Mounting And Mounting Flange Locations - Siemens SITRANS FUS1010 Guide Rapide

Masquer les pouces Voir aussi pour SITRANS FUS1010:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Quick Start Guide
Introduction
Application Guidelines

Mounting the Flowmeter

Temperature Ranges
Degree of Protection
Wall Mounting
Pipe Mounting
Notes:
1. Use conduit fittings or cable glands on all cables.
2. Install weather tight seals at all unused holes using proper cable conduit and close additional holes to
IP65 standards.
8

Preliminary Setup Procedures

This Quick Start Guide is for the Siemens Sitrans FUS1010 IP65 (NEMA 4X), FUH1010 IP65
(NEMA 4X), FUE1010 IP65 (NEMA 4X) Dual Channel flowmeters and the FUH1010 IP65 (NEMA
4X) Interface Detector. It illustrates a typical setup for the FUS1010 flowmeter using D-Series
transducers in the Reflect Mode (for Direct Mode see Flow Display Computer manual). These
procedures can also be applied to the single or multi-channel models as well.
Determine pipe material and dimensions
Pipe must be full during set-up.
Avoid vertical pipes flowing in a downward direction, if possible.
Avoid installation of transducers on the top and bottom of horizontal pipes, if possible.
Select a location with largest straight run of pipe.
Identify upstream piping configuration (elbow, reducer, etc.).
Pipe surface should be smooth and, if necessary, free of paint.
Avoid pressure reduction components upstream.
Avoid mounting on or near weld seams.
Operating Temperature Range:
Display Temperature Range:
IP65 NEMA 4X
The Flow Display Computer can be mounted on any wall surface including wood, metal or
concrete. Use the appropriate bolts and screws as needed for your mounting application
(not included). (See figure below for mounting flange locations.)
For installation on pipe use Pipe Mount Kit CQO:1012NMB-1 (optional-see catalog).
See figure below.
Figure 1. Pipe Mounting and Mounting Flange Locations
-18
C to 60
C (0
F to 140
F)
o
o
o
o
-18
C to 50
C (0
F to 122
F)
o
o
o
o
Pipe
Mounting Plate
Cable Entry Ports
Mounting Flange
(also use for wall
mounting)
U-Bolt Assembly for standard
2-inch (2.38 in. / 6.045 cm) pipe.
Flow Display
Computer

Publicité

Table des Matières
loading

Table des Matières