Quick Start Guide
Terminal Block Wiring
These connection diagrams apply to
the part numbers listed below.
1010N-2-7 (sh 2 of 2) Drawing
FUS1010 7ME353a-bc
where: a=0, 2 or 3
b=1 or 2
c= A, C or (Z=J1A)
FUE1010 7ME350a-bc
where: a = 0
b=1 or 2
c= D F or (Z=J1A)
FUH1010 7ME360a-bc
where: a=0, 2 or 3
b=0,1,2,3 or 4
c= A or (Z=J1A)
1010N-2-7 I/O Module
PGEN 1+
PGEN 1-
PGEN 2+
PGEN 2-

I/O Connections and Wiring

1010N-2-7 I/O Module
(Refer to manual drawing 1010N-2-7 sheet 2 of 2)
Table 1. INPUT/OUTPUT WIRING (TB2) - 1010N-2-7 I/O Module
PIN#
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Table 2. INPUT/OUTPUT WIRING (TB3) - 1010N-2-7 I/O Module
PIN#
1
2
3
4
5
6
7
8
9
10
11
12
13
14
TB-2
1
Analog Vo1
2
3
Analog Vo2
4
NC
5
6
Current Io1
7
8
Current Io2
9
NC
10
11
12
13
14
SIGNAL
FUNCTION
V o 1 +
0-10 Volt Analog Output
Vo1-
Ref. Ground
V o 2 +
0-10 Volt Analog Output
Vo2-
Ref. Ground
No Connection
Io1+
4-20mA Output 1
Io1-
ISOLATED RETURN
Io2+
4-20mA Output 2
Io2-
ISOLATED RETURN
No Connection
PGEN 1+
Frequency Output 1
PGEN 1-
Ref. Ground
PGEN 2+
Frequency Output 2
PGEN 2-
Ref. Ground
SIGNAL*
FUNCTION
K1 A
Relay 1 Normally Open
K1 B
Relay 1 Normally Closed
K1 C
Relay 1 Common
No Connection
K2 A
Relay 2 Normally Open
K2 B
Relay 2 Normally Closed
K2 C
Relay 2 Common
K3 A
Relay 3 Normally Open
K3 B
Relay 3 Normally Closed
K3 C
Relay 3 Common
No Connection
K4 A
Relay 4 Normally Open
K4 B
Relay 4 Normally Closed
K4 C
Relay 4 Common
+
0-10V
Load 10K ohm
-
(min)
+
0-10V
Load 10K ohm
-
(min)
+
4-20 mA
Load 1K ohm
-
(max)
+
4-20 mA
Load 1K ohm
-
(max)
}
To TTL/CMOS
+5V Logic Levels
}
To TTL/CMOS
+5V Logic Levels
DESCRIPTION
All Analog out-
puts assignable
to Vo, Vfo, Vs,
Valc and other
system variables
under menu
control.
0-5000 Hz
5 Volt Logic
S q u a r e
Waveform
DESCRIPTION
Assignment of
Relay functions
are under menu
control.
*Note:
A = N/O (Normally Open)
B = N/C (Normally Closed)
C = Common
TB-3
K1-A
1
*K1-B
2
3
K1-C
4
K2-A
5
*K2-B
6
7
K2-C
8
K3-A
9
*K3-B
10
K3-C
11
K4-A
12
*K4-B
13
K4-C
14
Note: Relays shown in Power OFF position, which is
the same as the alarm assertion position.
*Mercury Relay only available with Normally Open.
17