Building Air Conditioning Control System
Signal Receiving Unit
Installation Manual
This installation manual contains only the description of how to install the Signal Receiving Unit PAR-FA31MA. For information about
how to wire and how to install air conditioning units, see the installation manual for them.
For your safety, first be sure to read
FA31MA correctly.
1
Safety Precautions
The following two symbols are used to denote dangers that may be caused by incorrect use and their degree:
WARNING
This symbol denotes what could lead to serious injury or death if you misuse the PAR-FA31MA.
CAUTION
This symbol denotes what could lead to a personal injury or damage to your property if you misuse the PAR-FA31MA.
After reading this installation manual, keep it in a place where the final user can see it anytime he or she wants to it.
When someone moves, repairs or uses the PAR-FA31MA, make sure that this manual is forwarded to the final user.
Ask your dealer or technical representative to install the unit.
Any deficiency caused by your own installation may result in an elec-
tric shock or fire.
Install in a place which is strong enough to withstand the weight
of the PAR-FA31MA.
Any lack of strength may cause the PAR-FA31MA to fall down, re-
sulting in personal injury.
Firmly connect the wiring using the specified cables. Carefully
check that the cables do not exert any force on the terminals.
Improper wiring connections may produce heat and possibly a fire.
Never modify or repair the PAR-FA31MA by yourself.
Any deficiency caused by your modification or repair may result in
an electric shock or fire.
Consult with your dealer about repairs.
Do not install in any place exposed to flammable gas leakage.
Flammable gases accumulated around the body of PAR-FA31MA
may cause an explosion.
Do not use in any special environment.
Using in any place exposed to oil (including machine oil), steam and
sulfuric gas may deteriorate the performance significantly or give
damage to the component parts.
Wire so that it does not receive any tension.
Tension may cause wire breakage, heating or fire.
Completely seal the wire lead-in port with putty etc.
Any dew, moisture, cockroaches, insects entering the unit may cause
an electric shock or a malfunction.
Do not wash with water.
Doing so may cause an electric shock or a malfunction.
Do not install in any place at a temperature of more than 40 °C
or less than 0 °C or exposed to direct sunlight.
2
Confirming the Supplied Parts
Check that the box includes the following parts in addition to this installation manual:
(1) Signal Receiving Unit ......................................................... 1
(2) Remote control cord (2 core 3 m) ....................................... 1
NOTE: Extended remote controller cords are not supplied with this equipment and must therefore be procured locally by the customer.
Use electrical cable in accordance with the following specifications.
• 0.3 - 1.25 mm
Use a maximum of 1.25 mm
See the installation manual supplied with the outdoor unit for details of maximum wiring distances.
" 1 Safety Precautions "
2
twin-core cable (CVV, CVS, VVF)
2
cable for photo-electric adapter wiring. 0.75 mm
described below thoroughly and then install the Signal Receiving Unit PAR-
WARNING
Ensure that installation work is done correctly following this
installation manual.
Any deficiency caused by installation may result in an electric shock
or fire.
All electrical work must be performed by a licensed technician,
according to local regulations and the instructions given in this
manual.
Any lack of electric circuit or any deficiency caused by installation
may result in an electric shock or fire.
Do not move and re-install the PAR-FA31MA yourself.
Any deficiency caused by installation may result in an electric shock
or fire.
Ask your distributor or special vendor for moving and installation.
To dispose of this product, consult your dealer.
CAUTION
Do not install in any steamy place such a bathroom or kitchen.
Avoid any place where moisture is condensed into dew. Doing so
may cause an electric shock or a malfunction.
Do not install in any place where acidic or alkaline solution or
special spray are often used.
Doing so may cause an electric shock or malfunction.
Use standard wires in compliance with the current capacity.
A failure to this may result in an electric leakage, heating or fire.
Do not touch any PCB (Printed Circuit Board) with your hands
or with tools. Do not allow dust to collect on the PCB.
Doing so may cause fire or an electric shock.
Do not touch any control button with your wet hands.
Doing so may cause an electric shock or a malfunction.
Do not press any control button using a sharp object.
Doing so may cause an electric shock or a malfunction.
Never contact the power supply with the control wiring termi-
nals.
Doing so will certainly cause the controller to catch fire.
(3) Screw (M4 × 30) .................................................................. 2
(4) Wood screw (4.1 × 16) ........................................................4
2
PAR-FA31MA
wiring is recommended for ease of installation.
1

Publicité

Table des Matières
loading

Sommaire des Matières pour Mitsubishi Electric PAR-FA31MA

  • Page 1 CAUTION This symbol denotes what could lead to a personal injury or damage to your property if you misuse the PAR-FA31MA. After reading this installation manual, keep it in a place where the final user can see it anytime he or she wants to it.
  • Page 2: Example Of System Configuration

    Set the Main/Sub switch to “Sub” when using with the MA remote controller (PAR-20MAA). Adjuster switch Set the switch to adjustment on trial run. Pair number switch PAR-FA31MA (Factory setting “Normal”) Reset (Factory setting “0” ) After refiling batteries. Pair No. of receiver Seal Press the reset button.
  • Page 3: How To Install

    2 Setting example 2-1 When setting in same room. Separate setting Single setting Each unit can only be operated by its own wireless re- All the units can be operated by a single wireless remote con- mote controller. troller. “0” “1”...
  • Page 4 Bottom case (3) Installing hole when the Signal Receiving Unit is installed on the wall direct. Thin-wall protion • Cut the thin-wall portion inside the bottom case (oblique section) by a knife or a nipper. • Take out the connected remote control cord to the terminal brock through this space. (4) Seal the Signal Receiving Unit cord lead-in hole with putty in order to prevent the possible entry of dew, water droplets, cockroaches, other insects, etc.
  • Page 5: Télécommande De Réseau

    PAR-FA31MA Manuel d’installation Ce manuel d’installation contient uniquement les instructions relatives à l’installation de l’unité de réception des signaux PAR-FA31MA. Pour de plus amples informations concernant l’installation des climatiseurs ainsi que leur raccordement au secteur, reportez-vous à leur manuel d’installation.
  • Page 6: Exemple De Configuration Du Système

    Régler la position du commutateur de la télécommande et de l’unité de réception des signaux de la manière suivante: Régler l’interrupteur principal/secondaire sur “Sub” (secondaire) en cas d’utilisation avec une commande à distance MA (PAR-20MAA). Interrupteur de réglage Régler l’interrupteur sur “Set” pour l’essai de PAR-FA31MA Interrupteur de fonctionnement. Le numéro du ré- Reset correspondance des (Réglage d’usine sur...
  • Page 7: Comment Installer L'appareil

    2 Exemple de réglage Lors de l’installation dans une même pièce Installation séparée Installation unique Chaque appareil fonctionne uniquement à partir de sa propre Tous les appareils peuvent être contrôlés par une seule télécommande télécommande sans fil. sans fil. “0” “1”...
  • Page 8: Essai De Fonctionnement

    (3) Orifice de câblage pour une installation directe de l’unité de réception des signaux au Boîtier inférieur Fine portion de paroi mur. • Découper la fine portion de la paroi à l’intérieur du boîtier inférieur (section oblique) avec un couteau ou une pince coupante.

Table des Matières