Positioning The Device - Dräger X-zone 5500 Notice D'utilisation

Masquer les pouces Voir aussi pour X-zone 5500:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Establishing a wireless connection
4.3

Positioning the device

CAUTION
!
Before positioning the devices, a functional test (see
Chapter 3.4 on Page 43) must be conducted on every
device.
The device may heat up to a temperature outside the
specifications if it is used in very hot conditions and
under direct sunlight at the same time. This may result
in device failure or a reduced service life for some
device components. Dräger recommends placing the
device in the shade under these operating conditions.
NOTICE
i
i
The gas is supplied at an angle of 360°. If required, use
base (order no. 83 20 645) for a measuring position
raised by about 30 cm.
When positioning the devices, ensure that sub-
networks are avoided.
When used under constant vibration or in an inclined
position, harmful interference to proper operation may
occur. Do not operate the X-zone device under
constant vibration or from a tilted position.
1. Switch on the first X-zone (see Chapter 3.1 on Page 41)
and position at the relevant location.
2. Switch on the second
X-zone and position at a
distance that ensures the
communication LED lights
up green.
The wireless connection
is established and the
communication
LED
indicates the connection
to at least one device
within radio range.
WARNING
!
If the communication LED is lit in red, the distance from
the next device must be reduced.
Position other X-zone devices using the same process.
NOTICE
i
i
Dräger recommends performing a connection test
(see Chapter 3.4.3 on Page 43) after positioning all the
devices.
50
Examples of use:
Setting A:
Monitoring of industrial tanks (wireless alarm chain)
A
Setting B:
Area monitoring with pump
B
01333112.eps
Setting C:
Radio monitoring of pipelines (wireless alarm chain)
C
01833112.eps
01933112.eps
02033112.eps
Dräger X-zone 5500 / 5800

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

X-zone 5800Aac 0010Aac 0300

Table des Matières