Installation
3.3

Impedance of signal loop

Impedance range of the
Operating mode
signal loop
0 to 230 Ω
Rising linearly with the
Operation
supply voltage from:
without HART
0 to 230 Ω at 10 V to
communication
0 to 500 Ω at 16 V
0 to 500 Ω
230 to 270 Ω
Operation with
Rising linearly with the
HART
supply voltage from:
communication
230 to 270 Ω at 11 V to
(HART mode)
230 to 500 Ω at 16 V
230 to 500 Ω
HART Multidrop
operation
230 to 500 Ω
3.4

Mechanical installation

Use the drilling template for mounting on a flat surface.
The mounting surface should be even.
Dräger recommends using M6, 1/4" bolts with hex socket
caps.
The instrument must be accessible for maintenance (e.g.
calibration).
The future use of accessories and maintenance equipment
must be kept in mind.
The access of the gas or vapor to the sensor must not be
obstructed.
WARNING
!
Only for conduit installations: To reduce the risk of
Ignition of Hazardous Atmospheres, the conduit must
be sealed within 18" of the enclosure.
10
3.5
Supply
voltage range
!
at 10 V DC
10 to 18 V DC
Refer to the appropriate figure on the fold-out page and
proceed with the desired point.
18 to 30 V DC
at 13 V DC
Figure Connection diagram for
G
F
11 to 16 V DC
I
18 to 30 V DC
H
10 to 30 V DC
3.5.1
Refer to figure A on the fold-out page.
1. Loosen set-screw and unscrew lid from instrument.
2. Lift the handle and pull-out the PCB unit with the main
electronics.
3. Turn PCB unit over and pull off the 5-pin connector.
4. Connect the three wires for power and signal to the
appropriate terminal as indicated in the following wiring
table and figure F or G.
5. Fasten terminal screws with the correct torque according to
the table tightening torque and wire size for field wiring
terminal, see Section 10.10 on Page 44.
5-pin connector (voltage supply and current interface
Pin
Mark
Function V+
6. If operated as a stand alone instrument, wire pin 3 to pin4.
7. Plug connector back into socket and tighten screws.
8. The cable shielding should only be connected at the
controller
9. Place PCB unit back into the enclosure.
10. Screw the lid back on, until it is seated (see Section 10.9
on Page 44), and tighten set-screw.
3.5.2
Refer to figure A on the fold-out page.
1. Loosen set-screw and un-screw lid from instrument.
2. Lift the handle and pull-out the PCB unit with the main
electronics.
3. Turn PCB unit over and pull off the 2-pin and 4-pin
connector.
4. Connect the two wires for power and the four wires for
signal to the appropriate terminals as indicated in the
following wiring table and figure H or I.
Electrical installation without Docking
Station
CAUTION
Ensure wiring for relays and connections for sensor
are made before applying power.
Operation as a current source
Operation as a current sink
Profibus PA und Foundation Fieldbus H1
Modbus RTU

Electrical connection for 4-20 mA/HART interface

1
2
3
PWR+ PWR- PWR- 4-20 mA
V-
V-

Electrical connection for fieldbus interface

4
5
PE
4 to 20 mA signal
PE
(Operation as
source or sink)
Dräger Polytron 8100