5.2.4 Connecting Multiple Units to the Grid via Power Sockets
1. Each inverter's peak power can reach 2400W. Connecting multiple inverters to the same circuit can cause
!
the circuit to overload, leading to potential safety risks.
2. If your home does not have the required sockets and circuits, or if you lack the electrical knowledge
to accurately identify whether these sockets or circuits meet the requirements, please request the
assistance of an electrician. It is recommended to connect each inverter directly to a separate breaker.
For detailed instructions, refer to section 5.2.5.
3. The total maximum output power of all inverters is set to a default of 800W.(Country-specific limits:
France: 900W; Germany, Belgium, Netherlands, Austria, Italy: 800W; Switzerland: 600W;) If you need
to exceed this limit, please invite an electrician to your home to ensure your wiring is safe and does
not exceed the circuit load, or follow the installation guidelines in section 5.2.5 to connect each inverter
directly to the breaker. Then you can apply to increase the power via the Zendure App.
1. For Three-Phase Power: Connect each inverter to a socket on a dedicated circuit for each phase, ensuring no
other appliances are sharing the same circuit.
2. For Single-Phase Power: Connect the inverter to a socket on the dedicated circuit, without any other appliances
sharing the same circuit.
3. Press and hold the button for 2 seconds to power on each inverter.
Installation in three-phase electricity system
Electric Meter
Grid
Installation in single-phase electricity system
Electric Meter
Grid
Circuit Breaker
Circuit Breaker
Distribution Box
Circuit Breaker
Circuit Breaker
Circuit Breaker
Circuit Breaker
Distribution Box
Circuit Breaker
Circuit Breaker
9
Phase A
Phase B
Phase C
Phase A
Phase D